10.14 EVSE power rating
10.14.1 EVSE rating during normal duty operation
Normal duty operation applies for use in public applications with moderate traffic.
Parameter Specification [kW]
Terra 94 90
Terra 104 100
Terra 124 120
Terra 184 180
10.14.2 EVSE derating during normal duty operation
The table shows the steady state rating of the EVSE at specific ambient
temperatures.
Parameter
Specification
Ambient temperature Power Output [%] De-rating [%]
[°C] [°F]
-35 ... + 35 -31 … +95 100 0
+ 36 … + 40 +96 …+104 90 10
+ 41 … + 45 +105 …+113 85 15
+ 46 … + 50 +114 …+122 75 25
+ 51 … + 55 +123 …+131 65 35
The output power of the EVSE can be limited by the temperature of the charge
connector. This limitation can be caused by the connector model and rating, the EV
socket rating and the ambient conditions.
10.14.3 EVSE rating in heavy duty operation
Heavy duty operation applies for use in public applications with heavy traffic or
commercial/fleet applications.
Parameter
Specification [kW]
Terra 94 75
Terra 104 100
Terra 124 100
Terra 184 150
10.14.4 EVSE derating in heavy duty operation
The table shows the steady state rating of the EVSE at specific ambient
temperatures.
Technical data
88 9AKK108466A3703-EN | 001