EasyManuals Logo

ABB TRIO-20.0/27.6-TL-OUTD User Manual

ABB TRIO-20.0/27.6-TL-OUTD
131 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #116 background imageLoading...
Page #116 background image
- 116 -
000038FG
8 - Maintenance
- Message on display
- Signal
Name of Derating and Cause Solution
- LIMxxx% CODE:03
-
Display symbol b6
Anti-islanding power limitation:
The message indicates that a power limitation is active since an
"islanding" condition has been recorded.
LIM xxx% = Power reduction percentage
Examples:
LIM 100% = no power limitation
LIM 50% = limitation to 50% of the output nominal power
If the inverter remains connected to the grid and
the limitation is active, contact customer assistance
- LIMxxx% CODE:04
-
Display symbol b6
Power limitation due to low grid voltage:
The message indicates that an output power limitation may occur
since a low grid voltage (AC) condition has been recorded.
LIM xxx% = Power reduction percentage
Examples:
LIM 100% = no power limitation
LIM 50% = limitation to 50% of the output nominal power
• Check that the grid voltage is lower than the mini-
mal voltage. Should this condition persist, contact
the grid operator to resolve the problem.
- LIMxxx% CODE:05
-
Display symbol b7
Power limitation due to excess temperature:
The message indicates that a power limitation is active since an
excess temperature condition has been recorded inside the inver-
ter (This parameter depends also on the power which the inverter
must provide since the measurement of temperatures is taken
internally and is inuenced by the heat dissipated by the compo-
nents of the inverter itself).
LIM xxx% = Power reduction percentage
Examples:
LIM 100% = no power limitation
LIM 50% = limitation to 50% of the output nominal power
Check that the inverter is not exposed to direct
sunlight. Wait for the temperatures to which the in-
verter is exposed to return to the operating range
and for the inverter to cool down.
- If the problem (once the ambient temperature has
returned within the range) persists, contact custo-
mer assistance.
- LIMxxx% CODE:06
-
Display symbol b6
Power limitation for input over-voltage:
The message indicates that a power limitation is active since an
input over voltage (AC) has been recorded.
LIM xxx% = Power reduction percentage
Examples:
LIM 100% = no power limitation
LIM 50% = limitation to 50% of the output nominal power
• It is necessary to measure the input voltage inside
the inverter with a voltmeter.
- If it is higher than the maximum voltage of the ope-
rating range, the alarm is genuine and it is necessa-
ry to check the conguration of the PV generator. If
the voltage has also exceeded the maximum input
threshold the inverter could be damaged.
- If it is lower than the maximum voltage of the ope-
rating range, the alarm is caused by an internal
malfunction and it is necessary to contact customer
assistance.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB TRIO-20.0/27.6-TL-OUTD and is the answer not in the manual?

ABB TRIO-20.0/27.6-TL-OUTD Specifications

General IconGeneral
ModelTRIO-20.0/27.6-TL-OUTD
CategoryInverter
ManufacturerABB
Number of MPPT2
CoolingNatural convection
Protection ClassIP65
Max. AC Voltage400 V
AC Frequency50 / 60 Hz
MPPT Voltage Range200 - 800 V
Maximum DC Input Voltage1000 V
AC Output Voltage400 V
Operating Temperature Range-25°C to +60°C
Max AC Power20 kW
Rated Power Output20 kW

Related product manuals