2106001MNAA | XSERIES G5 START UP GUIDE | 75
a. Locate the COLDBOOT button (S9) and the RESET button (XFC S2
and XRC S6) on the electronic board.
b. Press and hold the COLDBOOT button and at the same time
press and hold the RESET button for 10 seconds.
c. The LCD displays Loading Boot Loader”.
d. Verify the Power On sequence is completed.
e. If the display moves through the startup screens and begins
cycling correctly, the COLDBOOT was successful.
f. If the display does not begin cycling correctly or locks up on one
of the startup screens, contact technical support for additional
instructions.
IMPORTANT NOTE:
To reach technical support, call the ABB Totalflow
main office, listed under Contact us: and select technical support
from the menu options.
Remote communication failure
IMPORTANT NOTE: Use COMM1 for remote communication.
Use the following list to eliminate possible remote communications issues
(in any order):
1. Verify that the symbol flashes in the A8 display position, see
Figure 13-1: XSeriesG5 annunciators
. This indicates that the port is
actively running Totalflow Remote Protocol. Each flash identifies
the Listen Cycle time period.
a. If the symbol is not flashing:
i. Set the port Listen Cycle to zero. The symbol should display
continuously.
ii. Select Totalflow Remote Protocol in the configuration of
the port, see 10.1: Configure COMM1
.
iii. Increase the cutoff voltage value specified in Station Setup
> Remote Comm Cutoff Voltage. This helps determine if
COMM1 is deactivated due to a drop in the voltage to the
device. The default is 11.9 Vdc. Use voltage values based on
the power mode used. Click Help in the Station Setup
screen for more details
2. Verify that these are correct:
a. The communication port wiring on the flow computer
b. The communication port wiring on the radio
c. All communication cables are intact and undamaged