11
3.4. Test Point Default Value
a. Control Logic Board: MS-I9919-x
Jumper Functions
JP1 Reserved
JP2 Reserved
JP3 Output Voltage Calibration
JP4(Default: Open for Internal Charger) Internal/External Charger Selection
JP5 Reserved
Driver Board:
1K(MS9917-
X)
2K(MSBD-
X)
MS3K(MSCD-
x)
Functions
JP1 JP2 JP1 Manual PFC Start-on Switch
JP2 JP1 JP3 Over-temperature Protection
JP3 JP3 JP2 Manual DC Booster Switch
3.5. Jumper Functions Explanation
a. Control Logic Board: MS-I9919-x
Jumper Functions
JP1 Reserved
JP2 Reserved
JP3 Output Voltage Calibration
JP4(Default: Open for Internal Charger) Internal/External Charger Selection
JP5 Reserved
Driver Board:
MS-D9917-x for 1K
& 2K
MSCD0xx for 3K Functions
JP1 JP1 Manual PFC Start-on Switch
JP2 JP3 Over-temperature Protection
JP3 JP2 Manual DC Booster Switch
3.6. Channel Function Explanation
Driver Board
MS1K MS2K MS3K Function
CN1 CN3 CN3 Connection with Logic Board
CN2 CN4 CN4 To Main Switch
CN3 CN1, CN2 CN1, CN2 To Fan
CN4 CN10 CN6 To the negative part of battery
CN5 CN9 CN5 To the positive part of battery
CN6 CN8 CN10 O/P Line
CN7 CN6 CN8 I/P AC Source Line
CN8 CN5 CN7 1. I/P AC Source Neutral
2. External Charger I/P Neutral
CN9 CN7 CN9 O/P Neutral
CN10 CN6 CN8 External Charger I/P Line
CN11 Reserved