16
4.2. Fault LED Lights up and No Output
4.2.1. Troubleshooting
FIG. 4.2
Check Items Trouble-shooting
Output Short Circuit Check if the output end of the UPS is in short
circuit.
Overload(>120%)
Reduce the output load.
MS1K/MS1KR: 1000VA/700W
Battery voltage is abnormal
1. If the battery voltage is under 28.8V, replace the batteries。
2. Remove the battery, check the charge voltage. If the voltage
please check U14、U10、VR1 and other device nearby.
INVERTER Voltage ERROR
Refer to fig.4-4, Check U7、U8、Q13、Q14 。