6.4 UPS Fails to Backup When Blackout
FIG. 6.4
Check Items Trouble-shooting
Battery is weak and no battery
charging current
When it is in charging mode.
Remove the harness of the battery from the
control board to measure the battery voltage. If
the voltage drops dramatically, please use a
switching power supply to charge the battery.
The charging voltage can be set at 115.2Vdc.
The battery shall be charged up to 80% of its
capacity.
Battery is defective Replace the battery with same size.
Battery harness is loose in
connection.
The current provided by the battery is approx. 20-
30A when it is at full
load. Please proceed to check any loose connection.
The IC of DC Booster stage is
out of order.
1.Check the related circuit is normal as shown in
fig. 6-5.
2.Check if the U7(IC SG
3525) is normal. Cut the Utility Source , remove
the battery and remove the control board, add a 96Vdc to CN5(+) and
CN6(-
) and 18Vdc to the pin 15 of U7 and short JP2 and check if the
pin 16 of U7 is 5.1V and pulses can be found at Pin 11 and Pin 14 of
U7. If not, please replace U7.
2.
The MosFETs (Q12, Q13, Q14, Q24, Q27, Q28) and
Diode(D32-D35) maybe abnormal, please check them.
DC to DC converter is
abnormal and/or the battery
fuse is defective.
1.Check the related circuit shown in fig. 6-5.
2.Check if (Q12, Q13, Q14, Q24, Q27, Q28)
and Diode(D32-D35) of the driver board are
defective.