EasyManua.ls Logo

Ablerex 3 MS series - 5.5. No LEDs and No Output

Ablerex 3 MS series
47 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
28
5.5 No LEDs and No Output
FIG. 5.5
Check Items Trouble-shooting
Power Devices defective, AC or DC fuse is burn Please see table 5.3 and 5.4 .
The working voltage of the control board is out
of order.
1.Please check the circuit shown in fig.5-2.
2.Cut off the Utility. Remove the control board.
Supply a 72Vdc to CN10(+) and CN9(-
Power supply, connect CN4 to the main switch.
Push on the main switch and to see if DC
POWER, i.e. VDD(17.5V), VCC(12V) and +/-
5V is normal.
Is normal.
4. Check if any abnormal output signal of the U9.
CPU is down. If the DC POWER is normal, the CPU could be
Down. Remove the battery harness from the
UPS and re-connect it back to its position.