SM01P 34
P10 TB-13A FUNCTION SELECT
P10 selects the function of terminal TB-13A. Closing TB-13A to TB-11 (or opening in
the case of settings 08 and 10) activates the selected function. The following functions
can be selected:
01 NONE: Disables the TB-13A function.
02 0-10 VDC: Selects a 0-10 VDC signal (at TB-5) as the AUTO speed reference
input.
03 4-20 mA: Selects a 4-20 mA signal (at TB-25) as the AUTO speed reference input.
04 PRESET SPEED #1: Selects PRESET SPEED #1 as the speed reference. The drive
will operate at the frequency programmed into Parameter 31.
05 START FORWARD: Sets up the drive for a 3-wire start/stop circuit. Momentarily close
TB-13A to TB-11 to start the drive, and momentarily open TB-1 to TB-11 to stop.
06 RUN REVERSE: Close TB-13A to TB-11 to run in the reverse direction, and open
to stop. Close TB-1 to TB-11 to run in the forward direction and open to stop.
07 START REVERSE: Momentarily close TB-13A to TB-11 to start the drive in the reverse
direction, and momentarily open TB-1 to TB-11 to stop. Parameter 17 - ROTATION
must be set to FORWARD AND REVERSE (02), and TB-13E must be used for
START FORWARD.
08 EXTERNAL FAULT: Sets TB-13A as a normally closed external fault input. Open
TB-13A to TB-11 to trip the drive.
09 INVERSE EXTERNAL FAULT: Sets TB-13A as a normally open external fault input.
Close TB-13A to TB-11 to trip the drive.
10 AUXILIARY STOP: When TB-13A is opened with respect to TB-11, the drive will
decelerate to a STOP (even if STOP METHOD is set to COAST) at the rate set into
ACCEL/DECEL #2 (Parameter 42).
11 ACCEL/DECEL #2: Selects the acceleration and deceleration time programmed into
ACCEL/DECEL #2 (Parameter 42).
P11 TB-13B FUNCTION SELECT
P11 selects the function of terminal TB-13B. Closing TB-13B to TB-11 (or opening in
the case of settings 09 and 11) activates the selected function. The following functions
can be selected:
01 NONE: Disables the TB-13B function.
02 0-10 VDC: Selects a 0-10 VDC signal (at TB-5) as the AUTO speed reference
input.
03 4-20 mA: Selects a 4-20 mA signal (at TB-25) as the AUTO speed reference input.
04 PRESET SPEED #2: Selects PRESET SPEED #2 as the speed reference. The drive
will operate at the frequency programmed into Parameter 32.