Installation and Commissioning Guide
Split Ducted Units
PRELIMINARY DATA ONLY Ver. 3.03 220620
THIS LABEL TO BE REMOVED ON SIGN-OFF
27
Installation and Commissioning Guide - Split Ducted Indoor Unit
Doc. No.0525-084 Ver. 3 22xxxx
Circuit Breaker Size and Cable Size Requirement
Model
Circuit Breaker Size Cable Size * (mm²)
Amps MAIN O.D. to I.D.
CRV140S/EVV140S 25.0 4.0
1.0
CRV160S/EVV160S
32.0 6.0
CRV180S/EVV180S
CRV160T/EVV160S
20.0 2.5
CRV180T/EVV180S
CRV210T/EVV210S
25.0 4.0 1.5
CRV240T/EVV240S
Notes:
1. Suggested Minimum Cable Size should be used as a guide only, refer to AS/NZS 3000 “Australian / New
Zealand Wiring Rules” for more details.