NetVanta 3000 Series Hardware Installation Guide Unit Installation
61200860L1-34L Copyright © 2006 ADTRAN, Inc. 67
NetVanta 3205 (DC)
The DC-powered NetVanta 3205 connects to a centralized DC power source via the three-position terminal
block on the rear of the chassis (see Figure 9 on page 29). Power and ground connections require copper
conductors and ring lugs.
Instructions for Connecting DC Power Source to the NetVanta 3205
Step Action
For +24 VDC operation:
1 Connect the negative terminal to ground.
2 Connect the positive terminal to the +24 VDC power source.
For -48 VDC operation:
1 Connect the positive terminal to ground.
2 Connect the negative terminal to the -48 VDC power source.
Power to the NetVanta 3205 DC System must be from a reliably grounded +24 or
-48 VDC source which is electrically isolated from the AC source.
Use only copper conductors when making power connections.
Install unit in accordance with Article 400 and 364.8 of NEC NFPA 70.
The branch circuit overcurrent protection shall be a fuse or circuit breaker rated
minimum 60 VDC, maximum 10 A.
A readily accessible disconnect device, that is suitably approved and rated, shall be
incorporated in the field wiring.
Maximum recommended ambient operating temperature is 50
°C.
The 10/100BaseT Ethernet interface MUST NOT be metallically connected to interfaces
which connect to the Outside Plant or its wiring. This interface is designed for use as an
intra-building interface only. The addition of primary protectors is not sufficient
protection in order to connect this interface metallically to OSP wiring.
To comply with GR-1089-CORE, Issue 3, this equipment MUST only be installed in a
DC-C (common) bonding and grounding environment. It may not be utilized in a DC-I
(isolated) bonding and grounding environment.

Table of Contents

Other manuals for ADTRAN NetVanta 3000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ADTRAN NetVanta 3000 Series and is the answer not in the manual?

ADTRAN NetVanta 3000 Series Specifications

General IconGeneral
BrandADTRAN
ModelNetVanta 3000 Series
CategoryNetwork Router
LanguageEnglish

Related product manuals