Operation and Display
C220/C420 General Flux Vector Control Inverter User Manual
54
the procedures for the automatic tuning of motor parameters are described
below
First, select the command source (F0-04)as the command channel of the
operation panel
Second, input the following parameters in accordance with the actual motor
parameters
Second, input the following parameters in accordance with the actual motor
parameters
F4-01: Rated motor power F4-02: Rated motor voltage
F4-04: Rated motor current F4-05: Rated motor Frequency
F4-06: Rated motor speed
If the motor cannot be completely disconnected with the load, select 2
(complete tuning) in F4-00,and then press RUN key on the keyboard panel, the
inverter will automatically calculate the following parameters
F4-07: no-load current F4-08: stator resistance
F4-09: Rotor resistance F4-10: mutual inductive reactance
F4-11: Leakage inductive reactance.
Finally, complete the automatic tuning of motor parameters
If the motor cannot be totally disconnected with the load, select 1 (static
tuning )in F4-00,and then press RUN key on the keyboard panel
Note: A suggestion from factory said that customer to select the way of
complete tuning which is able to help you acquire the motor parameters
more accurately.