Mechanical and Electrical Installation
C220/C420 Mechanical and Electrical Installation
33
3.2 Electrical installation
3.2.1 Guide to the selection of peripheral electrical parts
Tab.3-1 Guide to the Selection of Peripheral Electrical Parts of C220/C420Inverter
Inverter Model
Circu
it
Brea
ker
(MC
CB)
(A)
Recomm
ended
Contacto
r
(A)
Recom
mended
Input
Side
Main
Circuit
Wire
(mm²)
Recom
mended
Output
Side
Main
Circuit
Wire
(mm²)
Reco
mme
nded
Contr
ol
Circu
it
Wire
(mm²
)
PE
Wire
m
ADV 0.40 C220-M
16
10
2.5
2.5
1.5
2.5
ADV 0.75 C220-M
16
10
2.5
2.5
1.5
2.5
ADV 1.50 C220-M
20
16
4
2.5
1.5
2.5
ADV 0.75 C420-M
10
10
2.5
2.5
1.5
2.5
ADV 1.50 C420-M
16
10
2.5
2.5
1.5
2.5
ADV 2.20 C420-M
16
12
2.5
2.5
1.5
2.5
3.2.2 Use instruction of peripheral electric parts:
Tab.3-1 Guide to the Use Instruction of Peripheral Electric Parts of
C220/C420Inverter
Part Name
Installation
Location
Function Description
Circuit
breaker
The front-end
of the input
circuit
Disconnect the power supply in case of
Downstream equipment is over current.
Contactor
Between the
circuit
breaker
and the
inverter
input side
Power-on and power-off of the inverter. Frequent
power-on/power-
off operation on the inverter
shall be avoided.

Table of Contents