Parameter Description
C220/C420G General Flux Vector Control Inverter User Manual
57
control mode be taken advantage of, Better performance can be achieved by
adjusting the speed regulator parameters (Group F3).
F0-04
Command
source
selection
factory default value 0
setup
range
0
operation panel command channel
1
terminal command channel
2
serial port communication command channel
Select control command channel for inverter
The inverter control command includes start , stop, forward rotation ,reverse rotation
and Jog.
0: operation panel command channel(LED OFF)
Perform running command control with key on the operation panel such as
RUN , STOP/RES key
1: Terminal command channel (LED ON)
Perform running command control by the multifunctional input
terminals ,such as FWD、REV、JOGF、JOGR, etc.
2: Serial port command channel (LED flashes)
The running command is sent by the host computer via communication mode.
F0-06
Main frequency
source X
Factory default value 0
Setup
range
0
digital setup UP
、
DOWN(non-recorded)
1
digital setup UP
、
DOWN(recorded)
2
AI1