IST5 Tower UPS 10kVA~40kVA User Manual 15
Installation Instruction
3.5 Cable Entry
Cables can enter the UPS cabinet from the side or from the bottom. Cable entry is made
possible through a blanking plate fitted at the bottom of the equipment. The cable entry
is shown in Fig.3-11.
Cable connection
Cable connection
Fig.3-10 Cable entry
3.6 Power Cables
3.6.1 Specifications
The UPS power cables are recommended in Table 3.2.
Table 3.2 Recommended cables for power cables
Contents
10/15kVA
20/30kVA
40kVA
Main Input
Main Input Current(A)
18/28A
35/55A
70A
Cable Section
mm²)
A
6
10
16
B
6
10
16
C
6
10
16
N
6
10
16
Main Output
Main Output Current(A)
15/23A
30/45A
60A
Cable Section
mm²)
A
6
10
16
B
6
10
16
C
6
10
16
N
6
10
16
Bypass Input
Optional
Bypass Input Current(A)
15/23A
30/45A
60A
Cable Section
mm²)
A
6
10
16
B
6
10
16
C
6
10
16
N
6
10
16