Product Specification
50 IST5 Tower UPS 10kVA~40kVA User Manual
7. Product Specification
This chapter provides the specifications of the product, including environmental
characteristics mechanical characteristics and electrical characteristics.
7.1 Applicable Standards
The UPS has been designed to conform to the following European and international
standards:
Table 7.1 Compliance with
European and International
Standards
General safety requirements for UPS used in
operator access areas
EN50091-1-1/IEC62040-1-1/AS 62040-1-1
Electromagnetic compatibility (EMC)
requirements for UPS
EN50091-2/IEC62040-2/AS 62040-2
(
C3
)
Method of specifying the performance and
test requirements of UPS
EN50091-3/IEC62040-3/AS 62040-3
(
VFI SS
111
)
Note
The above mentioned product standards incorporate relevant compliance clauses with generic IEC
and EN standards for safety (IEC/EN/AS60950), electromagnetic emission and immunity (IEC/EN/
AS61000 series) and construction (IEC/EN/AS60146 series and 60950).
Warning
This product conforms the EMC requirements for UPS in Category C3
and it is not suitable for medical equipments.
7.2 Environmental Characteristics
Table 7.2 Environmental
Characteristics
Acoustic noise level
at 1 meter
58dB @ 100% load, 55dB @ 45% load
≤1000,load derated 1% per 100m from 1000m and
2000m
0-40,Battery life is halved for every 10°C increase
above 20°C