EN
11_11. 6755532_02
Cooling capacity
ALL ton 2,51 3,35 4,02
Total input power
H kW 2,81 3,85 4,32
HP-HA kW 3,01 4,05 4,52
ALL gpm 6,0 8,0 9,5
Pressure drop + piping H p.s.i. 1,1 1,3 2,0
H p.s.i. 0,2 0,4 0,5
ALL BTU/h 37670 51967 57598
Total input power
H kW 3,05 4,00 4,33
HP-HA kW 3,25 4,20 4,53
ALL gpm 8,4 11,5 12,8
Pressure drop + piping H p.s.i. 2,1 2,7 3,6
H p.s.i. 0,3 0,8 0,9
EER
H BTU/W 10,73 10,46 11,18
HP-HA BTU/W 8,94 9,94 10,68
COP
H W/W 3,62 3,81 3,89
HP-HA W/W 3,40 3,63 3,73
IPLV ALL - 4,36 4,25 4,53
ALL 220/1/60
H
A
14,2 16,9 18,3
HP-HA 15,1 17,8 19,2
Total input current cooling mode H 13,0 16,3 18,2
Total input current cooling mode HP-HA 13,9 17,2 19,1
ALL 45,0 45,0 45,0
MCA H 27,3 37,1 33,6
MCA HP-HA 28,3 38,1 34,6
MOP ALL 45,0 60,0 60,0
ALL n° 2 2 2
Total input power ALL cfm 244 244 244
ALL kW 0,3 0,3 0,3
EVAPORATOR
ALL n° 1 1 1
ALL inch 1" 1/4 1" 1/4 1" 1/4
ALL lb 9 12 13
N. compressors/circuits ALL n°/n° 1/1 1/1 1/1
Capacity control ALL - 0-100 0-100 0-100
Oil charge ALL oz 30 30 30
PUMP
Input power - kW 0,2 0,2 0,2
Input current - A 0,9 0,9 0,9
Useful head in cooling mode - p.s.i. 10,4 10,0 9,1
Useful head in heathing mode - p.s.i. 8,9 7,8 6,8
Storage tank - gal 26 26 26
Capacity - oz 169 169 169
- psi 22 22 22
- n° 1 1 1
Sound power - dBA 70,5 70,5 70,5
Sound pressure at 10 m - dBA 39,5 39,5 39,5
Height - in 50 50 50
Width - in 39 39 39
Depth - in 18 18 18
Empty weight "H" H lb 328 364 379
Empty weight "HP" HP lb 340 386 401
Height - in 50 50 50
Width - in 57 57 57
Depth - in 18 18 18
Empty weight "HA" HA lb 417 463 478
Outlet water temperature 6,7°C / 44,6°F
Flow rate 0,043l/s per kW
External temperature 35°C / 95°F
The total input power not include the pump.
Water input temperature 104°F / 40°C
Output water temperature 113°F / 45°C
External air temperature d.b./w.b. 44,6-42,8°F / 7-6°C
The reported data can be amended any time Aermec
considers it necessary.
Aermec determines sound power values in agreement with
the 9614-2 Standard, in compliance with that requested by
Eurovent certification.
Sound pressure measured in free field conditions with
from external surface of unit, in compliance with ISO 3744
regulations.