The choice and the installation of
components external to the ANK H
up to the installer, who must ope-
rate according to the rules of good
technical design and in compliance
with the regulations in force in the
country of destination.
The hydraulic pipes connecting to
the machine must be properly si
-
zed to the actual flow of water re-
quired by the system in operation.
The water flow to the exchanger
must always be constant.
Carefully wash the plant, before
connecting the unit. This allows
cleaning to remove any residue
such as weld spatter, slag, rust or
other impurities from the pipes.
These substances may otherwise
accumulate in and cause a machi
-
ne malfunction. The connecting
pipes should be supported so as
not to weigh, with their weight on
the unit
1
FL
3
5
5
12
6
6
2
4
4
11
11
9
7
8
4
10
13
14
PH 6-8
less than 200 mV/cm
less than 50 ppm
less than 50 ppm
less than 0.3 ppm
less than 50 ppm
less than 50 ppm
none
none
less than 30 ppm
Plate exchanger
Water filter
Flowswitch
Air Vent
Safety valve
Expansion tank
Pumps
Electrical heater 300W
Drain cock
6 anti vibration joints
7 Ball Stop
Storage tank
Manometer