EasyManuals Logo

AERMEC NSMI C-Touch User Manual

AERMEC NSMI C-Touch
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #12 background imageLoading...
Page #12 background image
12
7.3 ENABLES INPUT FILTERS AND COMPRESSORS
Indicates to which compressor the displayed data refers (U:1 = Master; U:2 =
Slave 1; U:3 = Slave 2; U:4 = Slave 3)
indicates the actual setting relating to the enabling of the delay to read the an-
alogue and digital inputs of the pCO5 board (YES = lters enabled; NO = lters
not enabled)
Indicates the value assigned to the delay in reading the analogue inputs of the
pCO5 board
Indicates the value assigned to the delay in reading the digital inputs of the
pCO5 board
Indicates the actual setting relating to the enabling (only from the master win-
dow U:1) of compressor 1 (YES= compressor enabled; NO = compressor not
enabled)
Indicates the actual setting relating to the enabling (only from the master win-
dow U:1) of compressor 2 (YES= compressor enabled; NO = compressor not
enabled)
Indicates the actual setting relating to the enabling (only from the master win-
dow U:1) of compressor 3 (YES= compressor enabled; NO = compressor not
enabled)
Indicates the actual setting relating to the enabling (only from the master win-
dow U:1) of compressor 4 (YES= compressor enabled; NO = compressor not
enabled)
Indicates the actual pressure value read at compressor intake
Indicates the actual pressure value read at compressor ow
7.4 ENABLING AND SETTING CONTROL VIA THE REMOTE
SUPERVISOR BMS
Indicates to which compressor the displayed data refers (U:1 = Master; U:2 =
Slave 1; U:3 = Slave 2; U:4 = Slave 3)
Indicates the current setting for ON/OFF via the supervisor (YES = function ena-
bled; NO = function disabled)
Indicates, only on heat pumps, the actual setting for the changeover from su-
pervisor (YES= function enabled; NO = function disabled)
Indicates the actual setting for the ON/OFF from digital input ID1 (YES= func-
tion enabled; NO = function disabled)
Indicates, only on heat pumps, the actual setting for the changeover from digi-
tal input ID2 (YES= function enabled; NO = function disabled)
Indicates the current address assigned to the unit for communicating with the
remote supervisor BMS1
Indicates the actual value assigned to the communication speed between the
unit and the BMS1 supervision system; the values that can be set are: 1200 or
19200 Baud
It can indicate (if the appropriate accessory serial interface board is provided
and properly installed) the actual protocol selected for communication be-
tween unit and BMS; the protocols available are:
Modbus RTU Slave = RS485 modbus supervisor;
CarelRS485 = communication protocol to pilot the expansion boards;
Bacnet = bacnet supervisor;
Lonworks = communication protocol to pilot the Lon expansion boards;
Indicates the current address assigned to the unit for communicating with the
remote supervisor BMS2
Indicates the actual value assigned to the communication speed between the
unit and the BMS2 supervision system; the values that can be set are: 1200 or
19200 Baud
Display only parameter, indicates the communication protocol for the Slave
compressors
7.5 OFFSET CONFIGURATION ON ANALOGUE INPUTS
1
2
3
4
5
10
11
6
7
9
8
12
13
14
15
16
1. Indicates to which compressor the displayed data refers (U:1 = Master; U:2 =
Slave 1; U:3 = Slave 2; U:4 = Slave 3)
2. Indicates the actual value to be added (or subtracted in case of negative val-
ues) as oset to the value read by the inlet water probe (if displaying the U:1
master page) or the evaporator water outlet (if displaying the Slave U:2, 3, 4
pages)
3. Indicates the actual value to be added (or subtracted in case of negative val-
ues) as oset to the value read by the probe placed at compressor ow
4. Indicates the actual value to be added (or subtracted in case of negative val-
ues) as oset to the value read by the evaporator outlet probe
5. Indicates the actual value to be added (or subtracted in case of negative val-
ues) as oset to the value read by the amperometric transformer
6. Indicates the actual value to be added (or subtracted in case of negative val-
ues) as oset to the value read by the multi-function input (if displaying the
U:1 master page) or the recovery outlet (if displaying the Slave U:2, 3, 4 pages)
7. Indicates the actual value to be added (or subtracted in case of negative val-
ues) as oset to the value read by the outside air probe
8. Indicates the actual value to be added (or subtracted in case of negative val-
ues) as oset to the value read by the temperature probe on the evaporator
gas side (only for units with recovery or freecooling)
9. Indicates the actual value to be added (or subtracted in case of negative val-
ues) as oset to the value read by the liquid temperature probe (only for units
with recovery or freecooling)
10. Indicates the actual value to be added (or subtracted in case of negative val-
ues) as oset to the value read by the recovery inlet water probe (for version
with recovery) or freecooling coil input (for freecooling units)
11. Indicates the actual value to be added (or subtracted in case of negative val-
ues) as oset to the value read by the recovery outlet water probe (for version
with recovery) or freecooling coil output (for freecooling units)
12. Indicates the actual value to be added (or subtracted in case of negative val-
ues) as oset to the value read by the probe placed at intermediate heat ex-
changer input (freecooling versions)
13. Not used
14. Indicates the actual set value for adjusting the condensation pressure calculat-
ed according to the outside temperature
15. Indicates the dierential applied to the actual set for adjusting the condensa-
tion pressure
16. Indicates the actual set for subcooling

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AERMEC NSMI C-Touch and is the answer not in the manual?

AERMEC NSMI C-Touch Specifications

General IconGeneral
BrandAERMEC
ModelNSMI C-Touch
CategoryControl Panel
LanguageEnglish

Related product manuals