7.10 SETTINGS FREE GLYCOL FREECOOLING
Indicates to which compressor the displayed data refers (U:1 = Master; U:2 =
Slave 1; U:3 = Slave 2; U:4 = Slave 3)
Indicates the value in kW declared for freecooling (circuit 1)
Indicates the value in kW declared for freecooling (circuit 2)
Indicates the value in kW declared for freecooling (circuit 3)
Indicates the value in kW declared for freecooling (circuit 4)
Indicates the value of compressor 1 in kW
Indicates the value of compressor 2 in kW
Indicates the value of compressor 3 in kW
Indicates the value of compressor 4 in kW
Indicates the dierential between the outside air and the water temperature at
unit inlet at which the freecooling power on circuit 1 is declared
Indicates the dierential between the outside air and the water temperature at
unit inlet at which the freecooling power on circuit 2 is declared
Indicates the dierential between the outside air and the water temperature at
unit inlet at which the freecooling power on circuit 3 is declared
Indicates the dierential between the outside air and the water temperature at
unit inlet at which the freecooling power on circuit 4 is declared
Indicates the outlet temperature from the freecooling coil below which the fans
are inhibited
Indicates the dierential (applied to the freecooling coil output) beyond which
the fans are enabled at maximum speed
Indicates the forcing time for the glycol pump at start-up
Indicates the activation set of the anti-freeze resistance for the glycol side
7.11 CONFIGURING THE CTOUCH CLOCK AND THE PCO5
CLOCK
Indicates to which compressor the displayed data refers (U:1 = Master; U:2 =
Slave 1; U:3 = Slave 2; U:4 = Slave 3)
Indicates the current day of the week on the C-Touch timer
Indicates the current time on the C-Touch timer
Indicates the current date on the C-Touch timer
Indicates the current time on the pCO5 timer
Indicates the current date on the pCO5 timer
Indicates the time to set on the pCO5 timer
Indicates the date to set on the pCO5 timer
Allows setting the specied date and time on the pCO5 board
7.12 SOFTWARE VERSION
Indicates to which compressor the displayed data refers (U:1 = Master; U:2 =
Slave 1; U:3 = Slave 2; U:4 = Slave 3)
Indicates the current software version for the pCO5 card