18
10 SUMMARY MENU
The SUMMARY menu provides a simplied representation of the unit with a selec-
tion of the operating parameters (in real time), on the basis of the feedback from
the various probes installed.
NOTE: The top-left corner of each window shows which compressor is currently
providing the displayed data (U:1,2,3 o 4); to switch between compressors (only
possible from Master unit), refer to that explained in paragraph "3.3Unit operating
status information (real time data)p.7".
10.1 PAGE RELATING TO THE COOLING ONLY UNITS
— Indicates to which compressor the displayed data refers (U:1 = Master; U:2 =
Slave 1; U:3 = Slave 2; U:4 = Slave 3)
— Indicates the actual speed of the fans
— Indicates the current outside temperature
— Indicates the status of the pump (if it's active, the relative label is displayed) and
the temperature of the water entering the heat exchanger
— Indicates the current operating set-point for the unit
— Indicates the actual status of the compressors (those displayed are the currently
active compressors, if no compressor is "On" no label will be displayed)
— Indicates the actual high pressure value for the currently selected circuit
— Indicates the actual low pressure value for the currently selected circuit
— Indicates the temperature of the water leaving the heat exchanger
— Indicates the heat exchanger inlet water temperature
10.2 PAGE RELATING TO THE UNITS WITH FREECOOLING
— Indicates to which compressor the displayed data refers (U:1 = Master; U:2 =
Slave 1; U:3 = Slave 2; U:4 = Slave 3)
— Indicates the current outside temperature
— Indicates the temperature of the water leaving the heat exchanger
— Indicates the actual speed of the fans
— Indicates the actual status of the compressors (those displayed are the currently
active compressors, if no compressor is "On" no label will be displayed)
— Indicates the actual high pressure value for the currently selected circuit
— Indicates the actual low pressure value for the currently selected circuit
— Indicates the heat exchanger inlet water temperature
— Indicates the status of the pump (if it's active, the relative label is displayed)
10.3 PAGE RELATING TO THE UNITS WITH FREE GLYCOL
FREECOOLING
— Indicates to which compressor the displayed data refers (U:1 = Master; U:2 =
Slave 1; U:3 = Slave 2; U:4 = Slave 3)
— Indicates the current outside temperature
— Indicates the temperature of the water leaving the heat exchanger
— Indicates the actual speed of the fans
— Indicates the actual status of the compressors (those displayed are the currently
active compressors, if no compressor is "On" no label will be displayed)
— Indicates the actual high pressure value for the currently selected circuit
— Indicates the actual low pressure value for the currently selected circuit
— Indicates the heat exchanger inlet water temperature
— Indicates the status of the pump (if it's active, the relative label is displayed)
10.4 PAGE RELATING TO THE UNITS WITH RECOVERY
— Indicates to which compressor the displayed data refers (U:1 = Master; U:2 =
Slave 1; U:3 = Slave 2; U:4 = Slave 3)
— Indicates the current outside temperature
— Indicates the water temperature from the recovery outlet
— Indicates the temperature of the water leaving the heat exchanger
— Indicates the actual speed of the fans
— Indicates the actual status of the compressors (those displayed are the currently
active compressors, if no compressor is "On" no label will be displayed)
— Indicates the actual high pressure value for the currently selected circuit
— Indicates the actual low pressure value for the currently selected circuit
— Indicates the water temperature at the recovery inlet
— Indicates the heat exchanger inlet water temperature
— Indicates the status of the pump (if it's active, the relative label is displayed)