EasyManua.ls Logo

Airwell Multi Split DUO 50 DCI - Pressure Curves

Airwell Multi Split DUO 50 DCI
62 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-1
PRESSURE CURVES
SM DUODCI 1-A.1 GB
6. PRESSURE CURVES
6.1 Model: FLO 9+25 DUO 50 DCI
6.1.1 Cooling – Test Mode
Suction Pressure Vs. Outdoor Temp’ - Cooling
700
800
900
1000
1100
1200
1300
1400
10 15 20 25 30 35 40 45
Outdoor DB Temperature[ºC]
Suction Pressure [kPa]
22/15
24/17
27/19
29/21
32/23
Dischar
g
e Pressure Vs. Outdoor Temp’- Coolin
g
1500
1750
2000
2250
2500
2750
3000
3250
3500
3750
4000
10 15 20 25 30 35 40 45
Outdoor DB Temperature[ºC]
Discharge Pressure [kPa]
22/15
24/17
27/19
29/21
32/23
Indoor
DB/WB
Indoor
DB/WB
CONTENT