2-3
PRODUCT DATA SHEET
SM DUODCI 1-A.1 GB
2.2.3 K 9 DCI Specifications
Model Indoor Unit / Type K 9 DCI / Cassette
Installation Method FLARE
Fan Motor Output W 36
Power Supply V/Ph/Hz 220-240 / 1/ 50
INDOOR
Fan Type & Quantity Centifugal *1
Airflow
(2)
Cooling / Heating
H/M/L m
3
/hr 530/600 500/530 435/450
Sound Power Level
(3)
Cooling / Heating
L - H dB (A) 42-48 / 42-47
Sound Pressure Level
(4)
Cooling / Heating
L - H dB (A) 32-38 / 32-37
Condensate Drain Tube I.D. mm 16
Dimensions W/H/D mm 571 287 571
Weight Kg 22.7
PacKage Dimensions W/H/D mm 685 415 685
StacKing Height Units 5
Heating Elements KW N/A
Moisture Removal L/hr 1
2.2.4 K 12 DCI Specifications
Model Indoor Unit / Type K 12 DCI / Cassette
Installation Method FLARE
Fan Motor Output W 36
Power Supply V/Ph/Hz 220-240 / 1/ 50
INDOOR
Fan Type & Quantity Centifugal *1
Airflow
(2)
Cooling / Heating
H/M/L m
3
/hr 580/620 510/560 435/450
Sound Power Level
(3)
Cooling / Heating
L - H dB (A) 42-49 / 42-48
Sound Pressure Level
(4)
Cooling / Heating
L - H dB (A) 32-38 / 32-38
Condensate Drain Tube I.D. mm 16
Dimensions W/H/D mm 571 287 571
Weight Kg 24.4
PacKage Dimensions W/H/D mm 685 415 685
StacKing Height Units 5
Heating Elements KW N/A
Moisture Removal L/hr 1.5
NOTE:
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN14511.
(2) Airflow in ducted units; at nominal external static pressure.
(3) Sound power in ducted units is measured at air discharge.
(4) Sound pressure level measured at 1 meter distance from unit.