EasyManua.ls Logo

ALBIN PUMP ALH - 4 Installation; Unpacking and Control; Conditions of Installation; Setup

ALBIN PUMP ALH
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10 albinpump@irco.com Albinpump.com Albin Pump ALH Instruction Manual
since 1928
ALH
Installation
DIMENSIONS
mm (Inch)
4 | INSTALLATION
4.1 - UNPACKING AND CONTROL
During the receipt of the pump, please follow the instructions printed on the packing. Make a visual inspection to insure that no
damage occurred during shipment. If this is the case, please contact your ALBIN PUMP distributor as soon as possible.
4.2 - CONDITIONS OF USE
ALH pumps can work in atmospheres where the temperature is situated between -20°C (-4°F) and 45°C (113°F). Pumps are
coated with a 150µ paint which will protect them against certain aggressive environments. They are designed for indoor and
outdoor setup.
4.3 - SET UP
Before installing the pump, check the following points:
- The pump is delivered with a frame provided with four anchoring holes. It must be xed on a solid base with a slope which
does not exceed 5mm for 1m and must be rmly fastened to this one.
- Require enough space around the pump to carry out maintenance. If such was not possible, consider the moving of the pump
to a space provided for this purpose.
- Make sure that the room is adequately ventilated to relieve the heat generated by the pump. Leave a space behind the motor
ventilator hood so as not to obstruct air intake.
4.4 - PIPING
Suction line piping:
- The internal diameter of the piping must be equal to or greater than that of the pump hose,.
- It must be the shortest and most direct possible to avoid suction loss.
- Suction pressures at higher operating pressures may cause the pump to rotate when the pump is disengaged. Above 1 bar,
consider adding a suction line valve to prevent this occurrence.
- Limit the presence of bends and make sure that they are as large as possible.
- Make sure that piping can support the service pressure of the pump.
Discharge line piping:
-The internal diameter of piping must be equal to or greater than to that of the pump hose, see §3.4.
- It must be the shortest and most direct possible to avoid discharge pressure loss.
- Limit the presence of bends and make sure that they are as large as possible.
- Provide a space for a pulsation dampener (see picture below).
- If there is a valve on the discharge line, install a pressure relief valve or an over pressure protection gauge to avoid any
possible damage to the pump and to the installation.
- It is recommended to install a exible line to help absorb pulsation.
During the pump ground study, provide enough space for the hose change as well as the possible installation of a pulsation
dampener. Distance (L) is the required length for hose removal.
L
PUMP L
ALH05 400 (15.7)
ALH10 400 (15.7)
ALH15 500 (19.7)
ALH20 500 (19.7)
ALH25 800 (31.5)
ALH32 1000 (39.4)
ALH40 1000 (39.4)
ALHX40 1200 (47.2)
PUMP L
ALH50 1400 (55.1)
ALH65 1400 (55.1)
ALHX65 1500 (59.0)
ALHX80 1600 (63.0)
ALH80 2000 (78.7)
ALH100 2800 (110.2)
ALH125 3000 (118.1)

Table of Contents