© Honeywell LT-MS4IOG Rev. 04 | Revised October 2015
47
INSTALLATION & OPERATIONS GUIDE | MICROSET 4
Object properties
Device object properties
PROPERTY ACCESS NOTES
Object Identifier R
Object Name R/W
Object Type R
System Status R OPERATIONAL
Vendor Name R Alerton
Vendor Identifier R 18
Model Name R MS4-TH
MS4-TH-NL
MS4-TH-MSTP
MS4-THC
Firmware Revision R RL 1.00 (build x)
Application Software Version R 1.00 (build y)
Location R/W
Description R/W
Protocol Version R 1
Protocol Revision R 4
Protocol Services Supported R atomicReadFile, atomicWriteFile, readProperty, readPropertyMultiple, writeProperty,
writePropertyMultiple, deviceCommunicationsControl, reinitializeDevice, i-Am,
unconfirmedPrivateTransfer, timeSynchronization, who-Has, who-Is,
utcTimeSynchronization
Protocol Object Types Supported R analog-input, analog-output, analog-value, binary-input, binary-output, binary-value,
device, file, program, schedule
Object List R Too large to return in a single request, so returns “segmentation not supported”.
Individual array entries can be read.
Max APDU Length Accepted R 480
Segmentation Supported R no-segmentation
Local Time R Default = “00:00:00”. Changed using TimeSync or UTCTimeSync.
Local Date R Default = “Jan 1, 1900". Changed using TimeSync or UTCTimeSync.
UTC Offset R/W Default = 0
APDU Timeout R/W Default = 6000, limited to 100..60000
Number of APDU Retries R/W Default = 3, limited to 0..16
Max Master R 127
Max Info Frames RW Default = 3, limited to 1..60
Device Address Binding R Empty List