86 Rockwell Automation Publication 1734-UM013N-EN-P - September 2017
Chapter 5 Configure the Module in a GuardLogix Controller System
5. To edit the Module Definition, click Change.
a. In the Series field, choose the input series letter of the module.
b. In the Revision fields, choose the input revision number of the module.
c. From the Electronic Keying pull-down menu, choose the appropriate
keying method for the input module.
d. From the Configured By pull-down menu, choose the appropriate
method by which this module is configured.
e. From the Input Data pull-down menu, choose Safety or None.
Choose Description
Exact Match All parameters must match or the inserted module rejects a connection to the
controller.
Compatible
Module
Allows an I/O module to determine whether it can emulate the module that is
defined in the configuration that is sent from the controller.
Choose Description
This Controller This selection directs the controller to configure the module.
External Means This selection directs the controller to establish a safety input connection only,
and the controller doesn’t configure the module or control the Test Outputs.
Choose Description
Safety These tags are created for the target module:
• RunMode for module mode
• ConnectionFaulted for communication status
• Safety Data for safety inputs from the module