Rockwell Automation Publication 1734-UM007E-EN-P - October 2015 35
Chapter 5
Diagnose Problems
About This Chapter
Read this chapter for information about how to troubleshoot using the module
indicators.
Use the Indicators for
Troubleshooting
Use these indicators to help you troubleshoot problems with your 1734-SSI
module.
Indication Probable Cause Recommended Action
Module Status
Off No power applied to device. Apply power to the device.
Flashing Green Device needs commissioning due to
configuration missing, incomplete, or
incorrect.
Configure device properly.
Solid Green Device is operating normally. None – device is operating normally.
Flashing Red Recoverable fault is present. Cycle power to device. If condition persists,
replace device.
Solid Red Unrecoverable fault may require device
replacement.
Unrecoverable fault may require device
replacement.
Flashing Red/Green Device is in self-test. None – device is in self-test.