EasyManua.ls Logo

Allen-Bradley 1756-L61S

Allen-Bradley 1756-L61S
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 1756-RM093J-EN-P - April 2018 105
Using 1794 FLEX™ I/O Modules and 1756 SIL 2 Inputs and Outputs with 1756 GuardLogix Controllers to Comply with EN 50156 Appendix G
SIL 2 Outputs Using SIL 3
Guard I/O Output Modules
Follow these guidelines for SIL 2 outputs:
The following list of Guard I/O™ output modules used for SIL 2 safety
outputs must be configured for dual-channel operation (all Guard I/O
output modules are approved for use in SIL 2 applications):
1732DS-IB8XOBV4
1791ES-IB8XOBV4
1791DS-IB8XOBV4
1791ES-IB8XOBV4
1791DS-IB4XOW4
1791DS-IB8XOB8
The following output modules are approved for use in SIL 2 applications,
using a single channel safety output:
1734-OB8S
1732ES-IB12XOB4
1732ES-IB8XOB8
SIL 2 Outputs Using 1756 or
1794 SIL 2 Output Modules
When using these SIL 2-rated output modules, you are required to configure
your SIL 2 safety outputs as GuardLogix-produced safety tags to comply with the
dual-channel requirements of EN 50156.
Create produced safety tags with the SIL 2 outputs that your application
requires. GuardLogix produced/consumed safety tags require the first member to
be allocated for diagnostics. The first member of a produced/consumed safety
connection must be a data type called CONNECTION_STATUS. This
example shows a SIL 2 tag with two INT and two BOOL members. Use these
SIL 2 safety tags to directly control the 1756 or 1794 SIL 2 outputs.
Follow all rules for 1756 I/O modules as defined in the Using
ControlLogix in SIL 2 Applications Safety Reference Manual, publication
1756-RM001
.
Follow all rules for 1794 FLEX I/O modules as defined in the FLEX I/O
System with ControlLogix for SIL 2 Safety Reference Manual, publication
1794-RM001
.
TIP
In this example, a consumer for the produced tag is not shown. The connection
status will show faulted if you don't configure a consumer. However, in this
type of configuration, you are not required to monitor the connection status of
the produced tag so the fault is not a concern.

Table of Contents

Related product manuals