Characteristics of Safety Tags, the Safety Task, and Safety Programs Chapter 5
Safety Tags
The GuardLogix control system supports the use of both standard and safety tags
in the same project. However, the programming software operationally
differentiates standard tags from safety tags.
Safety tags have all the attributes of standard tags with the addition of
mechanisms to provide SIL 3 data integrity.
RSLogix 5000 software prevents the direct creation of invalid tags in a safety
program. In the event that invalid tags are imported, they cannot be verified.
In safety programs on 1756-L6xS and 1768-L4xS controllers, RSLogix 5000
software also prevents the following:
The creation of a safety tag using a structured type (user-defined, Add-On
defined, predefined) when they contain one or more members of the
REAL data type, including nested structures.
The modification of a user-defined, or Add-On defined type that would
cause an invalid data type to be included when the user-defined or Add-
On defined type is already referenced directly or indirectly by a safety tag.
Invalid tags created by using with the New Tag or Tag Properties dialog
box.
Table 8 - Valid Data Types for Safety Tags
AUX_VALVE_CONTROL DINT MUTING_FOUR_SENSOR_BIDIR
BOOL DIVERSE_INPUT MUTING_TWO_SENSOR_ASYM
CAM_PROFILE
EIGHT_POS_MODE_SELECTOR
MUTING_TWO_SENSOR_SYM
CAMSHAFT_MONITOR EMERGENCY_STOP MOTION_INSTRUCTION
CB_CONTINUOUS_MODE ENABLE_PENDANT PHASE
CB_CRANKSHAFT_POS_MONITOR
EXT_ROUTINE_CONTROL PHASE_INSTRUCTION
CB_INCH_MODE EXT_ROUTINE_PARAMETERS
CB_SINGLE_STROKE_MODE FBD_BIT_FIELD_DISTRIBUTE REDUNDANT_INPUT
CONFIGURABLE_ROUT FBD_CONVERT REDUNDANT_OUTPUT
CONNECTION_STATUS FBD_COUNTER SAFETY_MAT
CONTROL FBD_LOGICAL SERIAL_PORT_CONTROL
COUNTER FBD_MASK_EQUAL SFC_ACTION
DCA_INPUT FBD_MASKED_MOVE SFC_STEP
DCI_MONITOR FBD_TIMER SFC_STOP
DCI_START FIVE_POS_MODE_SELECTOR SINT
DCI_STOP INT STRING
DCI_STOP_TEST LIGHT_CURTAIN THRS_ENHANCED
DCI_STOP_TEST_LOCK MAIN_VALVE_CONTROL TIMER
DCI_STOP_TEST_MUTE MANUAL_VALVE_CONTROL TWO_HAND_RUN_STATION
Aliasing between standard and safety tags is prohibited in safety
applications.