Rockwell Automation Publication 1756-RM093J-EN-P - April 2018 61
Safety Application Development Chapter 6
3. Check Inhibit Connection and click Apply.
The module is inhibited whenever the checkbox is checked. If a
communication module is inhibited, all downstream modules are also
inhibited.
Editing Your Safety
Application
The following rules apply to changing your safety application in RSLogix 5000
software:
Only authorized, specially-trained personnel can make program edits.
These personnel should use all supervisory methods available, for example,
using the controller keyswitch and software password protections.
When authorized, specially-trained personnel make program edits, they
assume the central safety responsibility while the changes are in progress.
These personnel must also maintain safe application operation.
When editing online, you must use an alternate protection mechanism to
maintain the safety of the system.
You must sufficiently document all program edits, including:
authorization.
impact analysis.
execution.
test information.
revision information.
If online edits exist only in the standard routines, those edits are not
required to be validated before returning to normal operation.
You must make sure that changes to the standard routine, with respect to
timing and tag mapping, are acceptable to your safety application.
You can edit the logic portion of your program while offline or online, as
described in the following sections.