34 1769-L32E, 1769-L35E CompactLogix Controller
Publication
1769-IN020-C-EN-P - July 2007
Module Status (MS) indicator
Condition Status Indicates Recommended Action
Off No power The controller does not have
po
wer.
Check the controller power supply.
Flashing green Standby The port does not have an IP
a
ddress and is operating in
BOOTP mode.
Verify that the BOOTP server is
running.
Solid green Ok The port is operating
co
rrectly.
Normal operation. No action
required.
Solid red Held in reset The controller is holding the
po
rt in reset or the controller
is faulted.
Clear the controller fault.
Replace the controller.
Self-test The port is performing its
p
ower-up self-test.
Normal operation during
power-up. No action required.
Major fault An unrecoverable fault has
o
ccurred.
Cycle power to the controller.
Replace the controller.
Flashing red Updating
fir
mware
The port firmware is being
updated.
Normal operation during firmware
update. No action required.