Rockwell Automation Publication 6000-IN006F-EN-P - March 2018 11
Drive Mechanical Installation Chapter 1
Figure 2 - Aligning Cabinets, Type B (6 kV shown)
Isolation Transformer CabinetPower Module/LV Control Cabinet
Table 2 - Sidesheet Openings
Front Wireway
U Phase Motor Cable
V Phase Motor Cable
W Phase Motor Cable
Ground Bus Connection
Voltage Sensing Board Cables
Isolation Transformer Secondary
Cables
(1)(2)
(1) The number of Isolation Transformer secondary
cables is dependent on motor voltage class.
• 9 cables per motor phase (27 total) for 3/3.3 kV
•12 cables per motor phase (36 total) for 4.16 kV
• 15 cables per motor phase (45 total) for 6 kV
•18 cables per motor phase (54 total) of 6.6 kV
•24 cables per motor phase (72 total) for 10kV
• 27 cables per motor phase (81 total) for 11 kV
(2) 6/6.6 kV configurations only require 18 cable hole
locations per phase. Extra cable hole locations allow
for added installation flexibility.
Front
Front
Side View