Programming and Parameters 3-35
DYNAMIC CONTROL
Restart Modes
169 [Flying Start En]
Enables/disables the function which
reconnects to a spinning motor at actual
RPM when a start command is issued.
Not required in FVC Vector mode when
using an encoder.
Default:
Options:
0
0
1
“Disabled”
“Disabled”
“Enabled”
170
170 [Flying StartGain]
Sets the response of the flying start
function.
Important: Lower gain may be required
for permanent magnet motors.
Default:
Min/Max:
Units:
4000
20/32767
1
169
174 [Auto Rstrt Tries]
Sets the maximum number of times the
drive attempts to reset a fault and restart.
Default:
Min/Max:
Units:
0
0/9
1
175
175 [Auto Rstrt Delay]
Sets the time between restart attempts
when [Auto Rstrt Tries] is set to a value
other than zero.
Default:
Min/Max:
Units:
1.0 Secs
0.5/30.0 Secs
0.1 Secs
174
File
Group
No.
Parameter Name & Description
See page 3-2 for symbol descriptions
Values
Related
ATTENTION: Equipment damage and/or personal injury may result
if this parameter is used in an inappropriate application. Do Not use
this function without considering applicable local, national and
international codes, standards, regulations or industry guidelines.
!