Programming and Parameters 3-41
UTILITY
Drive Memory
203 [Drive Checksum]
Provides a checksum value that indicates
whether or not a change in drive
programming has occurred.
Default:
Min/Max:
Units:
Read Only
0/65535
1
Diagnostics
209 [Drive Status 1]
Present operating condition of the drive.
Read Only 210
210 [Drive Status 2]
Present operating condition of the drive.
Read Only 209
211 [Drive Alarm 1]
Alarm conditions that currently exist in the drive.
Read Only 212
File
Group
No.
Parameter Name & Description
See page 3-2 for symbol descriptions
Values
Related
0110000001110000
10 01234567891112131415
1 =Condition True
0 =Condition False
x =Reserved
Bit #
Ready
Active
Command Dir
Actual Dir
Accelerating
Decelerating
Alarm
Faulted
At Speed
Local ID 0
(1)
Local ID 1
(1)
Local ID 2
(1)
Spd Ref ID 0
(2)
Spd Ref ID 1
(2)
Spd Ref ID 2
(2)
Spd Ref ID 3
(2)
Bits
(2)
Description
Bits
(1)
Description15 14 13 12 11 10 9
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
Ref A Auto
Ref B Auto
Preset 2 Auto
Preset 3 Auto
Preset 4 Auto
Preset 5 Auto
Preset 6 Auto
Preset 7 Auto
TB Manual
Port 1 Manual
Port 2 Manual
Port 3 Manual
Port 4 Manual
Port 5 Manual
Port 6 Manual
Jog Ref
0
0
0
0
1
1
1
1
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
Port 0 (TB)
Port 1
Port 2
Port 3
Port 4
Port 5
Port 6
No Local
Control
00000000000000xx
10 01234567891112131415
1 =Condition True
0 =Condition False
x =Reserved
Bit #
Ready
Active
Running
Jogging
Stopping
DC Braking
AutoTuning
DB Active *
AutoRst Ctdn
AutoRst Act
Curr Limit
Bus Freq Reg
Motor Overld
DPI at 500 k
* Vector firmware 3.001 & later
000000x00000000x
10 01234567891112131415
1 =Condition True
0 =Condition False
x =Reserved
Bit #
Prechrg Actv
UnderVoltage
Power Loss
Str At PwrUp
Anlg in Loss
IntDBRes OH
Drv OL Lvl 1
Drv OL Lvl 2
Decel Inhibt
Waking
Motor Therm *
In PhaseLoss *
Load Loss *
Ground Warn *
* Vector firmware 3.001 & later