EasyManua.ls Logo

Allen-Bradley PowerFlex 700H - Communication File

Allen-Bradley PowerFlex 700H
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 20C-PM001F-EN-P - March 2012 45
Programming and Parameters Chapter 2
Communication File
File
Group
No.
Parameter Name & Description Values
Related
COMMUNICATION
Comm Control
271 [Drive Logic Rslt]
The final logic command resulting from the combination of all
DPI and discrete inputs. This parameter has the same structure
as the product-specific logic command received via DPI and is
used in peer to peer communications.
1 = Condition True
0 = Condition False
Read Only
272 [Drive Ref Rslt]
Present frequency reference scaled as a DPI
reference for peer to peer communications. The
value shown is the value prior to the accel/decel
ramp and the corrections supplied by slip comp,
PI, etc.
Default:
Min/Max:
Units:
Read Only
–/+32767
1
273 [Drive Ramp Rslt]
Present frequency reference scaled as a DPI
reference for peer to peer communications. The
value shown is the value after the accel/decel
ramp, but prior to any corrections supplied by slip
comp, PI, etc.
Default:
Min/Max:
Units:
Read Only
–/+32767
1
Name
MOP Dec
Spd Ref ID 2
(1)
Spd Ref ID 1
(1)
Spd Ref ID 0
(1)
Decel 2
Decel 1
Accel 2
Accel 1
MOP Inc
Local Contrl
Reverse
Forward
Clear Fault
Jog
Start
Stop
Default0000000000000000
Bit 1514131211109876543210
Bits
(1)
Description14 13 12
0
0
0
0
1
1
1
1
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
No Command - Man. Mode
Ref A Auto
Ref B Auto
Preset 3 Auto
Preset 4 Auto
Preset 5 Auto
Preset 6 Auto
Preset 7 Auto

Other manuals for Allen-Bradley PowerFlex 700H