Rockwell Automation Publication 20C-PM001F-EN-P - March 2012 47
Programming and Parameters Chapter 2
COMMUNICATION
Masks/Owners
288 [Stop Owner]
Adapters that are presently issuing a valid stop command.
1 = Issuing Command
0 = No Command
Read Only 276
thru
285
289 [Start Owner]
Adapters that are presently issuing a valid start
command.
See [Stop Owner]
. 276
thru
285
290 [Jog Owner]
Adapters that are presently issuing a valid jog
command.
See [Stop Owner]
. 276
thru
285
291 [Direction Owner]
Adapter that currently has exclusive control of
direction changes.
See [Stop Owner]
. 276
thru
285
292 [Reference Owner]
Adapter that has the exclusive control of the
command frequency source selection.
See [Stop Owner]
. 276
thru
285
293 [Accel Owner]
Adapter that has exclusive control of selecting
[Accel Time 1, 2].
See [Stop Owner]
. 140
276
thru
285
294 [Decel Owner]
Adapter that has exclusive control of selecting
[Decel Time 1, 2].
See [Stop Owner]
. 142
276
thru
285
295 [Fault Clr Owner]
Adapter that is presently clearing a fault.
See [Stop Owner]. 276
thru
285
296 [MOP Owner]
Adapters that are currently issuing increases or
decreases in MOP command frequency.
See [Stop Owner]. 276
thru
285
297 [Local Owner]
Adapter that has requested exclusive control of all
drive logic functions. If an adapter is in local
lockout, all other functions (except stop) on all
other adapters are locked out and non-functional.
Local control can only be obtained when the drive
is not running.
See [Stop Owner]. 276
thru
285
Datalinks
300
301
[Data In A1] - Link A Word 1
[Data In A2] - Link A Word 2
Parameter number whose value will be written
from a communications device data table.
Value will not be updated until drive is stopped.
Refer to your communications option manual for
datalink information.
Default:
Min/Max:
Units:
0 (0 = “Disabled”)
0/486
1
302
303
[Data In B1] - Link B Word 1
[Data In B2] - Link B Word 2
See [Data In A1] -
Link A Word 1 [Data In A2]
- Link A Word 2.
File
Group
No.
Parameter Name & Description Values
Related
Name
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
DPI Port 6
DPI Port 5
DPI Port 4
DPI Port 3
DPI Port 2
DPI Port 1
Digital In
Defaultxxxxxxxxx0000000
Bit 1514131211109876543210

Other manuals for Allen-Bradley PowerFlex 700H

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 700H and is the answer not in the manual?

Allen-Bradley PowerFlex 700H Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex 700H
CategoryController
LanguageEnglish

Related product manuals