12 PowerFlex® 700S Drives - Phase I Control (Frame Sizes 9 & 10)
Step 4: Mounting the
Drive
Operating Temperatures
• For minimum mounting clearances and dimensions for frame 9 size drives, see
“Frame 9 Size Drives Mounting Clearances” below.
• For minimum mounting clearances and dimensions for frame 10 size drives, see
Frame 10 Size Drives Mounting Clearances
on page 14.
Also:
• For floor and wall mounting of frame 10 size drives, see Floor and Wall
Mounting for Frame 10 Size Drives on page 16.
Minimum Mounting Clearances and Dimensions
Frame 9 Size Drives Mounting Clearances
Frame Size
Surrounding Air Temperature
Required Airflow
m
3
/h (cfm) Voltage Class Amp Rating Normal Duty Heavy Duty
9 1300 (765) 400 261, 300 0 to 40 degrees C
(32 to 104 degrees F)
0 to 40 degrees C
(32 to 104 degrees F)
600 170 0 to 40 degrees C
(32 to 104 degrees F)
0 to 40 degrees C
(32 to 104 degrees F)
208 0 to 35 degrees C
(32 to 95 degrees F)
0 to 40 degrees C
(32 to 104 degrees F)
10 2600 (1530) 400 385, 460,
500
0 to 40 degrees C
(32 to 104 degrees F)
0 to 40 degrees C
(32 to 104 degrees F)
600 261, 325,
385
0 to 40 degrees C
(32 to 104 degrees F)
0 to 40 degrees C
(32 to 104 degrees F)
600 416 0 to 35 degrees C
(32 to 95 degrees F)
0 to 40 degrees C
(32 to 104 degrees F)
400.0 mm
(15.75 in.)
80.0 mm
(3.2 in.)
50.0 mm
(1.97 in.)
350.0 mm
(13.8 in.)
400.0 mm
(15.75 in.)
350.0 mm
(13.8 in.)
50.0 mm
(1.97 in.)