Programming and Parameters 3-7
PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22B-UM001I-EN-E
Display Group (continued)
d018 [Elapsed Run Time]
Accumulated time drive is outputting power. Time is displayed in 10 hour increments.
Values Default: Read Only
Min/Max: 0/9999 Hrs
Display: 1 = 10 Hrs
d019 [Testpoint Data] Related Parameter(s): A102
The present value of the function selected in A102 [Testpoint Sel].
Values Default: Read Only
Min/Max: 0/FFFF
Display: 1 Hex
d020 [Analog In 0-10V] Related Parameter(s): A110, A111
The present value of the voltage at I/O Terminal 13 (100.0% = 10 volts).
Values Default: Read Only
Min/Max: 0.0/100.0%
Display: 0.1%
d021 [Analog In 4-20mA] Related Parameter(s): A112, A113
The present value of the current at I/O Terminal 15 (0.0% = 4mA, 100.0% = 20mA).
Values Default: Read Only
Min/Max: 0.0/100.0%
Display: 0.1%
d022 [Output Power]
Output power present at T1, T2 & T3 (U, V & W).
Values Default: Read Only
Min/Max: 0.00/(Drive Rated Power × 2)
Display: 0.01 kW
d023 [Output Powr Fctr]
The angle in electrical degrees between motor voltage and motor current.
Values Default: Read Only
Min/Max: 0.0/180.0 deg
Display: 0.1 deg
22B-UM001.book Page 7 Tuesday, May 30, 2017 5:22 PM