Programming and Parameters 3-9
PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22B-UM001I-EN-E
Basic Program Group
P031 [Motor NP Volts] Related Parameter(s): d004, A084, A085, A086, A087
Stop drive before changing this parameter.
Set to the motor nameplate rated volts.
Values Default: Based on Drive Rating
Min/Max: 20/Drive Rated Volts
Display: 1 VAC
P032 [Motor NP Hertz] Related Parameter(s): A084, A085, A086, A087, A090
Stop drive before changing this parameter.
Set to the motor nameplate rated frequency.
Values Default: 60 Hz
Min/Max: 15/400 Hz
Display: 1 Hz
P033 [Motor OL Current] Related Parameter(s): A055, A058, A061, A089, A090,
A098
, A114, A118
Set to the maximum allowable motor current.
The drive will fault on an F7 Motor Overload
if the value of this parameter is exceeded by 150% for 60
seconds.
Values Default: Based on Drive Rating
Min/Max: 0.0/(Drive Rated Amps × 2)
Display: 0.1 Amps
P034 [Minimum Freq] Related Parameter(s): d001, d002, d013, P035, A085,
A086
, A087, A110, A112
Sets the lowest frequency the drive will output continuously.
Values Default: 0.0 Hz
Min/Max: 0.0/400.0 Hz
Display: 0.1 Hz
P035 [Maximum Freq] Related Parameter(s): d001, d002, d013, P034, A065,
A078
, A085, A086, A087, A111, A113
Stop drive before changing this parameter.
Sets the highest frequency the drive will output.
Values Default: 60 Hz
Min/Max: 0/400 Hz
Display: 1 Hz