EasyManua.ls Logo

Allen-Bradley PowerFlex40

Allen-Bradley PowerFlex40
160 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Programming and Parameters 3-27
PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22B-UM001I-EN-E
Advanced Program Group (continued)
A085 [Start Boost] Related Parameter(s): P031, P032, P034, P035,
A084
, A086, A087, A088, A125
Sets the boost voltage (% of P031 [Motor NP Volts]) and redefines the Volts per Hz curve when A084
[Boost Select] = 0 “Custom V/Hz” and A125 [Torque Perf Mode] = 0 “V/Hz”.
Drive may add additional voltage unless Option 5 is selected.
Values Default: 2.5%
Min/Max: 0.0/25.0%
Display: 0.1%
Frequency
Voltage
A087 [Break Frequency] P032 [Motor NP Hertz]
P035 [Maximum Freq]
A085 [Start Boost]
P031 [Motor NP Volts]
A088 [Maximum Voltage]
A086 [Break Voltage]
A034 [Minimum Freq]
A086 [Break Voltage] Related Parameter(s): P031, P032, P034, P035,
A084
, A085, A087, A088, A125
Sets the frequency where break voltage is applied when A084 [Boost Select] = 0 “Custom V/Hz” and
A125 [Torque Perf Mode] = 0 “V/Hz”
Values Default: 25.0%
Min/Max: 0.0/100.0%
Display: 0.1%
A087 [Break Frequency] Related Parameter(s): P031, P032, P034, P035,
A084
, A085, A086, A088, A125
Sets the frequency where break frequency is applied when A084 [Boost Select] = 0 “Custom V/Hz
and A125 [Torque Perf Mode] = 0 “V/Hz”
Values Default: 15.0 Hz
Min/Max: 0.0/400.0 Hz
Display: 0.1 Hz
22B-UM001.book Page 27 Tuesday, May 30, 2017 5:22 PM