3-12 Functional Blocks
DOCHANNEL
PWMCHANNEL
Description Generates status output (0 or 1), pulsed output (ON or OFF) for specified pulse time based on origin of input and
parameters.
Function • Brings SO or PO from connected blocks and stores value in an associated IOM block.
• Sets INITVAL parameter to appropriate value based on echo data.
• Stops SO if INTREQ is TRUE
• Sets INITREQ to TRUE value if DOC or IOM block is inactive or a communications error occurs.
• You can configure PO to be Direct or Reverse by connecting ONPULSE or OFFPULSE pin.
Inputs Only one control block can interface to this block.
Outputs Digital (Boolean) value or pulsed (real) value.
Associated
Block
Prior to loading, block must be “associated” with 1 channel of corresponding IOM block that interfaces with physical
DO hardware module at execution runtime.
Parameters BACKCALCOUT
BADCODE
DEBUG
DOMSO
DOTYPE
EXECCOUNT
FETCHMODE
FREEZETIME
INITREQ
INITVAL
IOCNUMBER
IOCSTATE
IOCTYPE
IOMCONN
LASTSERIAL
NOFIELDPWR
NOLOAD
OFFPULSE
ONPULSE
ORDERINCM
SHORT
SO
SOSOURCE
UPDATOPT
VERIFYLOST
Description Provides a pulse width modulated output signal for operating final control elements in combination with a DO
Module.
Function • Brings OP data from connected block and stores data in an associated IOM block.
• Sends out a pulse based on the configured pulse width period (PWMPERIOD) with its duty cycle determined by the
OP data.
• Sets INITVAL parameter to appropriate value based on echo data.
• Assigns safe value if status parameter is BAD or UNCERTAIN.
• Sets INITREQ to TRUE (ON) value if CM containing PWMC block or IOM block is inactive or a communications error
occurs. If communication fails, the pulse function terminates. So, be sure you select the proper SHED VALUE for
the DOM channel to reflect the desired inactive digital state.
Inputs OP value from another block. Typically, output in 0 to 100% from a PID block, which indicates the proportion of time
period that the output will be turned on.
Outputs Pulsed (real) value
Associated
Block
Prior to loading, block must be “associated” with 1 channel of corresponding IOM block that interfaces with physical
DO hardware module at execution runtime.
Parameters BACKCALCOUT
BADCODE
COMMFAILFL
DEBUG
DOMSO
EXECCOUNT
FETCHMODE
FREEZETIME
IOCNUMBER
IOCSTATE
IOCTYPE
IOMCONN
INITREQ
INITVAL
NOFIELDPWR
NOLOAD
OP
OPSOURCE
ORDERINCM
PWMPERIOD
SHORT
VERIFYLOST