Publication 1757-RM810A-EN-P - May 2002
Functional Blocks 3-31
XOR
Regulatory Control Blocks
AUTOMAN (Auto Manual)
Description Provides an up to 8-input XOR algorithm, meaning it performs the exclusive OR function. Each input (IN [1], IN [2], ...,
IN [8]) has the capability of being optionally inverted, if required.
Function Turns output (OUT) ON only if an odd number of inputs are ON; otherwise, OUT is OFF.
Truth Table IN [1]
OFF
ON
OFF
ON
IN [2]
OFF
OFF
ON
ON
OUT
OFF
ON
ON
OFF
Inputs IN [1..8] = Boolean value
Outputs OUT = Boolean value controlled by the status of input signals.
Parameters IN [1..8]
INPTINVSTS [1..8]
ORDERINCM
OUT
Description Applies a user-specified gain and bias as well as a calculated bias (OPBIAS.FLOAT) to the output. The user-specified
values can be fixed or external. A fixed value is stored manually or by a program, and an external value is brought from
another function block.
Function Provides control initialization and override feedback processing. Typically used either:
in cascade control strategy where an upstream block may not accept an initialization request from its secondary,
between FANOUT block and a final control element to provide bumpless output on return to cascade.
Timeout
Monitoring
In cascade mode, performs timeout monitoring on the input (X1). If the X1 value is not updated within a predefined
time, this block invokes the following timeout processing:
1. Sets the input timeout flag (TMOUTFL).
2. Sets the input value to Bad (NaN).
3. Requests the X1 primary to initialize.
This block does not support mode shedding on timeout.
Inputs X1 = initializable input which must come from another function block; an operator cannot set it.
XEUHI and XEULO define the full range of X1:
XEUHI is the value that represents 100% of full scale.
XEULO is the value that represents 0% of full scale.
Outputs Block has following initializable outputs:
OP = Calculated output in percent.
OPEU = Calculated output in engineering units
Note that the default OP connection pin is exposed on the blocks and the implicit/hidden connection function
automatically makes the appropriate value/status parameter (OPX/OPEUX) connection when required.
More on following page
Spare Allen-Bradley Parts

Table of Contents

Questions and Answers: