3-46 Functional Blocks
PULSELENGTH
Description Generates pulse trains according to its pulse length control algorithm. The pulsed outputs are usually fed to Digital
Output Channel blocks.
Dual Pulse Length: A control algorithm turns on either a raise channel or a lower channel after every execution of
this algorithm. The selected output stays on for a time period that is calculated by the control algorithm. The
calculated on-duration will be in 10 msec increments.
Single Pulse Length: A single output channel is used to indicate the direction (raise or lower) of the actuator. A
second output channel is used to indicate the calculated on-duration (or length) of the pulse. The calculated
on-duration will be in 10 msec increments.
Function Typically used in conjunction with a POSPROP block to step a valve open or closed, raise or lower a rotary device,
or move the plates of a pulp mill refiner together or apart.
The POSPROP block feeds the PULSETIME input parameter to the PULSELENGTH block. This parameter is an
internal structure that contains the pulse width specification (in seconds). It also contains a Serial Number that
changes every time there is a new pulse width value. The PULSELENGTH block checks for a change in the Serial
Number before reacting to the pulse width specification.
Inputs Requires a pulse time (PULSETIME) input from another block. A POSPROP block usually supplies this.
The PDELAYDIRCHG input is user configurable in seconds.
The optional LOCALMAN input should come from another block in a logic strategy where an ON condition means
that the CEE is not controlling the output of the device.
Outputs The PULSELENGTH block has the following initializable outputs:
PORAISE = Pulse output for Raise pulses. These pulses are generated if the pulse width specified by the
PULSETIME input is positive.
POLOWER = Pulse output for Lower pulses. These pulses are generated if the pulse width specified by the
PULSETIME input is negative.
PO = Pulse output for both Raise and Lower pulses. These pulses are generated as a logical OR between the
PORAISE and POLOWER pulses.
PODIR = Direction for PO. This output is OFF for a Lower pulse and is ON for a Raise pulse.
Parameters ALMDB
ALMDBU
ALMTM
INITMAN
INITREQ
LOCALMAN
ORDERINCM
PDELAYDIRCHG
PO
PODIR
POLOWER
PORAISE
PULSETIME

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley ProcessLogix 1757 Series and is the answer not in the manual?

Allen-Bradley ProcessLogix 1757 Series Specifications

General IconGeneral
BrandAllen-Bradley
ModelProcessLogix 1757 Series
CategoryControl Unit
LanguageEnglish

Related product manuals