0180036-J0 Rev E Page 16
Weight: 200 grams (0.440 lb.)
Voltage Inputs: 4 BiV (-60 to ±60Vdc)
Shunt Inputs: 4 (25 to 200Mv)
Analog Inputs: 4 DC voltage, 4 DC current, 4 temperature
Digital Inputs: 8, plus dedicated LVD override
Relay Outputs: 12 Form C, 60Vdc 1A maximum
6I-ADIO
Power: 10-60Vdc, 5W
Front Panel Controls: Recessed reset button
LED’s: Power (Blue), Comms (Green)
Mounting: 3U 19/23” Rack Mounting
DIN Rail Mounting - option
Panel Mounting - option
Dimensions: 84mm H x 31mm W x 30mm D (5.1" x H x 16.9" W x 3.9" D)
Weight: 200 grams(0.440 lb.)
Shunt Inputs: 6 (25 to 200mV)
Analog Inputs: 6 DC current ±200mV
Communication Ports: CAN In/CAN Out
Recommended Connection Wire Sizes (per UL/CSA)
Wire Size Range: #16 to #26 AWG
CAUTION: TO REDUCE RISK OF FIRE, USE ONLY #26 AWG (0.14mm2) OR LARGER WIRE. Ensure
any wiring to bus voltages is appropriately protected with fuses or circuit breakers.
Table 2: Specifications: 3RU Rack Mount CXC HP (Continued) (Sheet 4 of 4)
Cordex Controller Panel/Rack Mount