%5HY
7DEOH* ² /LQH6WDWXV
Normal
The line is within specifications. See specifications, “Boost/Buck/Line Transfer Thresholds”.
The Alpha FXM is operating in Line mode.
Boost
Line voltage is out of tolerance. The Alpha FXM is operating in Boost mode.
Boost2
Line voltage is out of tolerance. The Alpha FXM is operating in Boost 2 mode.
Buck
Line voltage is out of tolerance. The Alpha FXM is operating in Buck mode.
Buck2
Line voltage is out of tolerance. The Alpha FXM is operating in Buck 2 mode.
Blackout
The line is absent.
Freq low
Line frequency is too low.
Freq high
Line frequency is too high.
6.9.1 Line Status
Line status tells you the line’s condition. For an updated value, press Enter.
7DEOH+ ² 2XWSXW6WDWXV
Line mode
Battery mode
Battery mode, low bat. warning
Battery mode (testing battery)
Boost mode
Boost 2 mode
Buck mode
Buck 2 mode
Hot swap mode
Inverter off due to fault
Inverter off due to low battery
Inverter off at start-up
Shutdown due to user request
6.9.2 Output Status
Output status tells you how the Alpha FXM is producing power. For an updated value, press Enter.