30
A01-00055 Rev N
North American Models ABCE802-11 and ABCE802-11MED
ABCE802-11
50080-03R
ABCE802-11MED
50080-23R
Type Standard Medical Grade
Power Rating (VA/Watts) 800 / 720 800 / 720
Inverter Waveform Low Distortion Sine Wave Low Distortion Sine Wave
Transfer Time 4 ms. Typical 4 ms. Typical
Frequency 60 Hz. 60 Hz.
BTU/Hr. 231 231
T.H.D. w/100% Resistive Load <4% on Battery <4% on Battery
Online Efciency (w/o Charger) 91% 91%
Input Voltage 120 120
Input Current 9.35 Amps 9.35 Amps
Output Voltage 120 120
Output Current (VA/Watts) 6.70 / 6.00 Amps 6.70 / 6.00 Amps
Input Voltage Range
(w/o Using Battery)
96 to 144 Volts 96 to 144 Volts
Output Regulation (On Mains) ± 10% ± 10%
Output Regulation (On Battery) ± 5% ± 5%
Backup Time at Full Load (0.7 P.F.) 5 Minutes 5 Minutes
Floor Mountable Yes (Optional) Yes (Optional)
Communications Interface DB9, USB (SNMP Optional) DB9, USB (SNMP Optional)
Shipping Weight (lbs.) 49 49