34
A01-00055 Rev N
North American Models ABCE1442-11 and ABCE1442-11MED
ABCE1442-11
50144-03R
ABCE1442-11MED
50144-23R
Type Standard Medical Grade
Power Rating (VA/Watts) 1440 / 1296 1440 / 1296
Inverter Waveform Low Distortion Sine Wave Low Distortion Sine Wave
Transfer Time 4 ms. Typical 4 ms. Typical
Frequency 60 Hz. 60 Hz.
BTU/Hr. 459 459
T.H.D. w/100% Resistive Load <4% on Battery <4% on Battery
Online Efciency (w/o Charger) 91% 91%
Input Voltage 120 120
Input Current 12.00 Amps 12.00 Amps
Output Voltage 120 120
Output Current (VA/Watts) 12.00 / 10.80 Amps 12.00 / 10.80 Amps
Input Voltage Range
(w/o Using Battery)
96 to 144 Volts 96 to 144 Volts
Output Regulation (On Mains) ± 10% ± 10%
Output Regulation (On battery) ± 5% ± 5%
Backup Time at Full Load (0.7 P.F.) > 5 Minutes > 5 Minutes
Floor Mountable Yes (Optional) Yes (Optional)
Communications Interface DB9, USB (SNMP Optional) DB9, USB (SNMP Optional)
Shipping Weight (lbs.) 71 71