A01-00055 Rev N
International Models ABCE1442-22 and ABCE1442-22MED
ABCE1442-22
51144-03R
ABCE1442-22MED
51144-23R
Type Standard Medical Grade
Power Rating (VA/Watts) 1440 / 1296 1440 / 1296
Inverter Waveform Low Distortion Sine Wave Low Distortion Sine Wave
Transfer Time 4 ms. Typical 4 ms. Typical
Frequency 50 / 60 Hz. 50 / 60 Hz.
BTU/Hr. 292 292
T.H.D. w/100% Resistive Load <4% on Battery <4% on Battery
Online Efciency (w/o Charger) 94% 94%
Input Voltage 230 230
Input Current 8.54 Amps 8.54 Amps
Output Voltage 230 230
Output Current (VA/Watts) 6.30 / 5.65 Amps 6.30 / 5.65 Amps
Input Voltage Range
(w/o Using Battery)
185 to 276 volts 185 to 276 volts
Output Regulation (Mains) ± 10% ± 10%
Output Regulation (On Battery) ± 5% ± 5%
Backup Time at Full Load (0.7 P.F.) > 5 Minutes > 5 Minutes
Floor Mountable Yes (Optional) Yes (Optional)
Communications Interface DB9, USB (SNMP Optional) DB9, USB (SNMP Optional)
Shipping Weight (kg) 32 32