Specications
Allbelowvaluesarebasedon96kWand160kWmaximumcongurations.Ifthecablesandcurrent
protectionareconguredfora96kWsystem,onlysixpowermodulesmustbeinstalledinthesystem.To
upgradetoa160kWsystem,aredimensioningofcablesandcurrentprotectionsisrequired.
Caution:Allelectricalpowerandpowercontrolwiringmustbeinstalledbyaqualied
electrician,andmaycomplywithlocalandnationalregulationsformaximumpowerrating.
ACInputSpecications
96kW160kW
380V400V415V380V400V415V
Connectiontype
3PH+N+G
Inputfrequency(Hz)
40–70
THDI
<5%atfullload
Nominputcurrent(A)
1
154146141256243234
Maxinputcurrent(A)
2
169160155281267258
Inputcurrentlimitation(A)
3
197197197295295295
Inputpowerfactorcorrection>0.98atload>50%
1
Inputcurrentbasedonnominalvoltageandratedload,batteriesfullycharged
2
Inputcurrentbasedonfullbatteryrecharge,nominalvoltageandratedload
3
Currentlimitationthroughelectroniccurrentlimitingisbasedonfullratedloadandlimitedbatteryrecharge
from-10%to-15%inputvoltage
ACBypassInputSpecications
96kW160kW
380V400V415V380V400V415V
Connectiontype
3PH+N+G
Inputfrequency(Hz)
40–70
Nominputcurrent(A)
147139134243231223
ACOutputSpecications
96kW160kW
380V400V415V380V400V415V
Connectiontype
3PH+N+G
Outputcapacity150%for30seconds(normaloperation)
125%for10minutes(normaloperation)
150%for30seconds(batteryoperation)
125%for10minutes(batteryoperation)
125%continuous(bypassoperation)
1000%for100ms(bypassoperation)
Nomoutputcurrent(A)
147139134243231223
2
SymmetraPX96and160kW400VInstallation
990–3017E-001