Specications
Allbelowvaluesarebasedon96kWand160kWmaximumcongurations.Ifthecablesandcurrent
protectionareconguredfora96kWsystem,onlysixpowermodulesmustbeinstalledinthesystem.To
upgradetoa160kWsystem,aredimensioningofcablesandcurrentprotectionsisrequired.
Caution:Allelectricalpowerandpowercontrolwiringmustbeinstalledbyaqualied
electrician,andmaycomplywithlocalandnationalregulationsformaximumpowerrating.
ACInputSpecications
96kW160kW
380V400V415V380V400V415V
Connectiontype
3PH+N+G
Inputfrequency(Hz)
40–70
THDI
<5%atfullload
Nominputcurrent(A)
1
154146141256243234
Maxinputcurrent(A)
2
169160155281267258
Inputcurrentlimitation(A)
3
197197197295295295
Inputpowerfactorcorrection>0.98atload>50%
1
Inputcurrentbasedonnominalvoltageandratedload,batteriesfullycharged
2
Inputcurrentbasedonfullbatteryrecharge,nominalvoltageandratedload
3
Currentlimitationthroughelectroniccurrentlimitingisbasedonfullratedloadandlimitedbatteryrecharge
from-10%to-15%inputvoltage
ACBypassInputSpecications
96kW160kW
380V400V415V380V400V415V
Connectiontype
3PH+N+G
Inputfrequency(Hz)
40–70
Nominputcurrent(A)
147139134243231223
ACOutputSpecications
96kW160kW
380V400V415V380V400V415V
Connectiontype
3PH+N+G
Outputcapacity150%for30seconds(normaloperation)
125%for10minutes(normaloperation)
150%for30seconds(batteryoperation)
125%for10minutes(batteryoperation)
125%continuous(bypassoperation)
1000%for100ms(bypassoperation)
Nomoutputcurrent(A)
147139134243231223
2
SymmetraPX96and160kW400VInstallation
990–3017E-001

Table of Contents

Other manuals for APC Symmetra PX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the APC Symmetra PX and is the answer not in the manual?

APC Symmetra PX Specifications

General IconGeneral
Noise level61 dB
Output power32000 W
Output power capacity32 kVA
Emergency Power Off (EPO)Yes
Battery typeVRLA
Dimensions (WxDxH)1200 x 1070 x 1991 mm
Battery technologySealed Lead Acid (VRLA)
Battery recharge time3.5 h
CertificationEN 50091-1, EN/IEC 62040-3, EN/IEC 62040-1-1, FCC Part 15 Class A, VFI-SS-111
Product colorBlack
Operating altitude0 - 999.9 m
Non-operating altitude0 - 15000 m
Storage temperature (T-T)-15 - 40 °C
Operating temperature (T-T)0 - 40 °C
Operating relative humidity (H-H)0 - 95 %
Weight and Dimensions IconWeight and Dimensions
Weight1095400 g
Package weight1189000 g