5.4. APR–2000GALW, Measurement ranges and metrological parameters.
5.4.1 APR–2000GALW. Measurement ranges
N°
Nominal range
(FSO)
Minimum set range
Overpressure
limit
Static pressure limit
1 0...25mbar (0...2500Pa) 1mbar (100Pa) 1bar 350mbar
2 -2,5...2,5mbar (-250...250Pa) 0,2mbar (20Pa) 350mbar 350mbar
3 -7...7mbar (-700...700Pa) 1mbar (100Pa) 350mbar 350mbar
4 -25...25mbar (-2500...2500Pa) 5mbar (500Pa) 1bar 1bar
5 -100...100mbar (-10...10Pa) 20mbar (2kPa) 1bar 1bar
5.4.2. APR–2000GALW. Metrological
parameters
.
Nominal range
0...25mbar -2,5...2,5mbar
-100...100mbar
Accuracy
≤ ± 0,075 % ≤ ± 0,16 % ≤ ± 0,1 % ≤ ± 0,1 % ≤ ± 0,075 %
Thermal error
± 0,1 % (FSO)/ 10°C, max ± 0,4 % (FSO) for the whole thermal compensation
range
Thermal compensation range -10 … 70
C
Additional electronic damping 0...60 s
5.4.3. APR–2000GALW. Construction materials
M20x1,5/∅6x1 adapter brass
Valve manifold ss316L
Valve manifold adapter ss316L
¼ NPT connector brass, ss316L or galvanized St3S carbon steel
(Other materials as given in 5.1.3 for APR...).
5.4.4. APR–2000GALW. Pressure Connectors
- The terminals fit adapted to ø 6x1 plastic tubes,
- Valve manifold adapter or ¼ NPT connector- (see p. 8.3. and fig.17).
5.5. APR–2000YALW. Measurement ranges and metrological parameters.
5.5.1. APR–2000YALW. Measurement ranges.
5.5.2. APR–2000YALW. Metrological parameters.
* zeroing in static pressure conditions with zero differential pressure eliminate this error.
Medium density range – up to 1,1 g/cm
3
– (standard version)
– over 1,1 g/cm
3
– (special version by arrangement with APLISENS
)
N° 1 2
Nominal range
0... – 6000 mmH
2
O 0... – 1600 mmH
2
O
Minimum set range
600 mmH
2
O 160 mmH
2
O
Static pressure limit 40 bar
Nominal range N°
1 2
Accuracy for basic range ± 0,16 % ± 0,2 %
Accuracy for minimum range ± 0,5 % ± 0,6 %
temperature error 0,4 % for temperatures –25...+80°C
Zero shift error from static pressure * 0,08 % / 10bar 0,1 % / 10bar