3.2.18 Impulse Outputs Fout1 … Fout3 Menu
Output State - parameter setting the state of the device impulse output, which enables
frequency generation proportional to the measured power. The parameter value
is ACTIVE ENERGY for the frequency generation proportional to the measured
active power, REACTIVE ENERGY for the frequency generation proportional to
the measured reactive power, APPARENT ENERGY for the frequency
generation proportional to the measured apparent power, FIXED for constant
frequency generation and OFF for impulse output switched-off, respectively.
Channel Lx - parameter setting the selection of individual channels (L1, L2 or L3) for impulse
output functions. The value of the parameter is ON or OFF for the switched-on or
switched-off selection of the appropriate channel, respectively.
Fixed freq. - frequency value on the device impulse output in case that “State” parameter is
in the state “FIXED”.
Energy Factor -parameter setting the device impulse output multiplicity constant if the parameter
“State” is in the state ACTIVE ENERGY, REACTIVE ENERGY or APPARENT
ENERGY, respectively. Generated frequency is proportional to the product of this
constant and sum of measured values of the given type of power in the selected
channels. These channels are given in “Channel Lx” parameters placed in the
Energy menu. Unit of showed value is in 1/Ws (1/Vas, 1/Vars) or 1/kWh (1/kVAh,
1/kVArh) and depends on values of Energy Factor and Factor Unit parameters.
Energy F. Unit - parameter setting the unit in which the value of parameter Energy Factor is
showed. Parameter is 1/Ws (1/Vas, 1/Vars) or 1/kWh (1/kVAh, 1/kVArh).
3.2.19 Impulse Input Fin Menu
Fin Meas/Test -> - start of Frequency Input screen (measurement is started immediately)
Fin Config … - Frequency Input Configuration menu
MUT Constant - parameter setting the constant of Meter Under Test
MUT Const. Unit - parameter setting the unit in which the value of parameter MUT Constant is
showed. Parameter is 1/Ws (1/Vas, 1/Vars) or 1/kWh (1/kVAh, 1/kVArh).
Int. Time - parameter setting the integration time for Fin measurement
3.2.20 Frequency Input Configuration Menu
Input State - parameter setting the state of the device frequency input which is proportional
to some type of measured power. The parameter value is ACTIVE ENERGY for
the frequency input proportional to the measured active power, REACTIVE
ENERGY for the frequency input proportional to the measured reactive power or
APPARENT ENERGY for the frequency input proportional to the measured
apparent power, respectively.
Channel Lx - parameter setting the selection of individual channels (L1, L2 or L3) for impulse
input functionality. The value of the parameter is ON or OFF for the switched-on
or switched-off selection of the appropriate channel, respectively.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Applied Precision RS 2130 and is the answer not in the manual?

Applied Precision RS 2130 Specifications

General IconGeneral
BrandApplied Precision
ModelRS 2130
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals